Especificaciones:
INPUT
Dual Input: no
Rated power: 6000 VA
Voltage: 220-230-240 Vac
Voltage tolerance: 140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
Frequency: 50/60 Hz ± 5 Hz
Frequency tolerance: 50 Hz ± 20% / 60 Hz ± 20%
Power factor: >0.98
Current distorsion: _5%
BY PASS
Voltage tolerance: 180÷264 Vac (selectable in Economy Mode and SMART ACTIVE Mode)
Frequency tolerance: Selected frequency ± 5% (user configurable)
Number phases: 1
OUTPUT and INVERTER OUTPUT
Rated power: 6000 VA
Active power: 6000 W
Crest factor (Ipeak/Irms): 3 : 1
Waveform: Sinewave
Frequency: 50/60 Hz selectable
Voltage distortion with distorcing load: <6%
Voltage distortion with linear load: <3%
Inverter efficiency at rated load: 95%
OVERLOAD TIMES
100% < Load < 110%: activates the bypass after 10 min Continues to work on by-pass
110% < Load < 133%: activates the bypass after 1 min shut down after 1 hour
133% < Load < 150%: activates the bypass after 5 s shut down after 10 min
Load > 150%: activates the bypass instantaneously shutdown after 3 s (load > 150%) shutdown after 2 s (load > 200%)